Neskeb - FRLS
Cable Standard
Generally conforms to IS 694:2010, BS6004
Salient Features(FR and FRLS)
- REACH, ROHS, CE and CPR Compliant
- Anti-Rodent, Anti-Termite
- 100% Electrolytic Copper
- More than 101% Conductivity
Technical Data
Voltage Grade : Up to and including 1100VApprovals :IS 694 marked, FIA/TAC
Operating Temp : 10°Cto max.+90°C
Nominal Voltage : 1.1 KV
Test Voltage : 3.0 KV
Flame propagation: Flame retardant test
as per IS 10810-58,64, IEC 60332-1
Data Sheet
Standard Packing
Coils 90m, 180m and 360m
Conductor : Thin strands of electrolytic copper are multi-drawn for uniformity of resistance, dimension and flexibilityInsulation : Specially formulated flame retardant low smoke low halogen compound to restrict the spread of flames in fire situation. The smoke emitted by the burning cable is considerably low compared to traditional cables. This ensures improved visibility for evacuation of trapped victims and facilitates fire fighting operation.
Insulation Conformity : IS 5831 Type A/D FR-LSH 70°C
Marking :The cables are printed with marking of "NESKEB FR" from 1 Sq. mm to 6 Sq. mm
Packing : 90 mtr. coil is packed in protective cartons upto size 6 Sq. mm. Project packing of 180 mtr. also available.
Core Colour
Red, yellow, blue, black, green, grey & white
Application
Suitable for wiring in all types of residential and commercial infrastructure, where fire and electrical safety is utmost important.
Wire Size | No. of wire / Diameter of Wire | Insulation Thickness | OD | Max Conductor Resistance at 20°C | Current Rating |
---|---|---|---|---|---|
sq.mm | No./mm | mm | mm | 2/km | Amps |
0.50 | 16/0.20 | 0.60 | 2.10 | 39.0 | 4 |
0.75 | 10/0.30* OR 24/0.20 | 0.60 | 2.40 | 26.0 | 8 |
1.0 | 14/0.30 OR 32/0.20 | 0.60 | 2.65 | 18.10 | 11 |
1.5 | 22/0.30* OR 30/0.250 | 0.70 | 3.0 | 12.10 | 13 |
2.5 | 36/0.30* OR 50/0.250 | 0.80 | 3.6 | 7.41 | 18 |
4.0 | 56/0.30 | 0.80 | 4.0 | 4.95 | 24 |
6.0 | 84/0.30 | 0.80 | 5.1 | 3.30 | 31 |
10.0 | 140/0.30 | 1.0 | 6.3 | 1.91 | 52 |
16.0 | 224/0.30 | 1.0 | 8.0 | 1.21 | 70 |
* Class-2 Conductor    * If Required Tinned copper conductor also available
Test FRLS | Specification | Specified Values |
---|---|---|
Limited Oxygen Index Test | IS 10810-58 | > 29% |
Limited Temperature Index Test | IS 10810-64 | > 250°C |
Smoke Density Rating(Light Absorption) | ASTM D 2843 | < 60% |
Halogen Acid Gas Generation | IS 10810-59 | < 20% |