Cable Assist

Motor Output Unit: Select Output Size: ⚡ 415 V | 3-Phase | 50 Hz
Full Load Current
Line Current
1 AMP
Phase Current
0.6 AMP
Direct Online (DOL) Starter
Overload Relay Range
1.5 - 3 AMP
Max Backup Fuse
4 AMP
Recommended Cable Size
2.5 Sq. MM Al 1.5 Sq. MM Cu
Star Delta Starter
Overload Relay Range
--
Max Backup Fuse
--
Cable Size (Supply Side)
-- --
Cable Size (Motor Side)
-- --
📢 Recommendation Note: We recommend 6 Core cable between Star Delta starter and Motor. If 6 Core cable is not available, use 2 Nos. of 3 Core unarmoured cables.
Conductor Cross Section Area:
📝 Technical Notes & Standards (IS:3961):
  • Values in Grey (Ground) are Current Ratings for cables laid in Ground.
  • Values in Red (Air) are Current Ratings for cables laid in Air.
  • For approximation, the current rating for Power cables with Copper Conductors increases over the listed Aluminum rating by roughly 25%.
  • The rating values shown are standard normal ratings and subject to de-rating factors based on environment conditions.

Building Wires - FR

Single Core, Twin Insulated Wires in Voltage Grade 650/1100 V (Flame Retardant)

Nominal Cross Section Area Of Conductor (Sq. mm) Max Resistance / km @ 20°C (Ohms/Km) Current Carrying Capacity (AMPs)
0.75 Sq. mm 26.00 8 AMPs
1.0 Sq. mm 18.10 13 AMPs
1.5 Sq. mm 13.30 17 AMPs
2.5 Sq. mm 7.98 24 AMPs
4.0 Sq. mm 4.95 31 AMPs
6.0 Sq. mm 3.30 40 AMPs